FIREGUARD® and FLAMESHIELD® tanks are both STI/SPFA aboveground steel storage tank technologies used for flammable and combustible liquid storage. Both are double-wall tanks that can provide secondary containment and interstitial monitoring capability, and both are available through STI/SPFA licensed fabricators.

The main difference is the level and type of fire protection.

FIREGUARD® is a UL 2085 listed protected aboveground storage tank. It includes an inner and outer steel tank with a lightweight thermal insulation material between the walls. It is designed as a protected tank to limit heat transfer from the tank exterior to the tank interior and includes features such as thermal insulation between the primary and secondary tank, integral secondary containment, interstitial monitoring, and impact and ballistics protection per UL 2085.

FLAMESHIELD® is a fire-tested, double-wall aboveground steel storage tank. It uses a tight-wrap double-wall design and is tested to meet the 2-hour, 2,000°F fire test requirements of Southwest Research Institute Standard SwRI 97-04.  This heat exposure test is similar to the one used in the UL 2085 certification process.  A FLAMESHIELD® tank provides built-in secondary containment and interstitial monitoring capability, but it does not use thermal insulation and is not the same as a UL 2085 listed protected tank.

Quick Comparison Table

TopicFIREGUARD®FLAMESHIELD®
Basic descriptionProtected, thermally insulated, double-wall aboveground storage tankFire-tested, tight-wrap, double-wall aboveground storage tank
Primary standard/listing contextUL 2085 listed protected tankUL 142 double-wall tank with SwRI 97-04 fire-tested performance
Fire protection approachUses lightweight thermal insulation between the inner and outer steel tanks to limit heat transferUses a non-insulated tight-wrap double-wall design that has passed a 2-hour, 2,000°F fire test
Protected tank statusYes, UL 2085 listed protected tankNo, fire-tested double-wall tank, but not the same as a UL 2085 protected tank
Impact and ballistics protectionIncludes ballistics and impact protection per UL 2085Not positioned as a UL 2085 impact- and ballistics-protected tank
Secondary containmentBuilt into the protected tank systemBuilt into the double-wall tank system
Interstitial monitoringInterstitial space can be monitored for leak detectionInterstitial space can be monitored for leak detection
InsulationIncludes lightweight thermal insulation materialNon-insulated tank design
Common applicationsProjects requiring or preferring UL 2085 protected tanks, enhanced fire resistance, impact protection, or AHJ/code-driven protectionProjects requiring a fire-tested double-wall tank where UL 2085 protected tank status is not required
Typical decision questionDoes the project require a UL 2085 protected aboveground tank?Is a fire-tested double-wall UL 142 tank acceptable for the application?

What Is a FIREGUARD® Tank?

A FIREGUARD® tank is an STI/SPFA protected, thermally insulated, double-wall aboveground storage tank. It features an inner and outer steel tank with a lightweight thermal insulation material between the walls.

FIREGUARD® tanks are UL 2085 listed protected tanks. They are designed to provide enhanced thermal protection of the primary tank, and the tanks contents, from exterior heat sources like fire, as well as integral secondary containment, interstitial monitoring capability, and ballistics and impact protection per UL 2085.

FIREGUARD® tanks are used for aboveground storage of compatible flammable and combustible liquids, including common fuel storage applications such as gasoline, diesel, biodiesel, ethanol blends, aviation fuel, and generator fuel. Final suitability depends on the stored product, tank design, project specification, applicable codes, and authority having jurisdiction.

What Is a FLAMESHIELD® Tank?

A FLAMESHIELD® tank is an STI/SPFA fire-tested, double-wall aboveground steel storage tank. It uses a tight-wrap double-wall design with built-in secondary containment and interstitial monitoring capability.

FLAMESHIELD® tanks are tested to the 2-hour, 2,000°F fire test requirements of Southwest Research Institute Standard SwRI 97-04. The fire test validates the performance of non-insulated tanks and confirms it can withstand the heat exposure without compromising the tank’s integrity.

FLAMESHIELD® tanks are commonly used when a project needs a fire-tested, double-wall aboveground storage tank, but the application does not require a UL 2085 listed protected tank.

Key Differences Between FIREGUARD® and FLAMESHIELD® Tanks

Protected Tank vs. Fire-Tested Tank

The most important difference is classification.

FIREGUARD® is a UL 2085 listed protected aboveground storage tank. UL 2085 protected tanks include additional protection features such as enhanced thermal protection of the stored contents, integral secondary containment, and impact protection.

FLAMESHIELD® is a fire-tested, double-wall aboveground tank. It is tested under SwRI 97-04 and is manufactured as a double-wall UL 142 tank, but it is not the same as a UL 2085 listed protected tank.

This distinction matters because project specifications, fire codes, insurers, or the authority having jurisdiction may require one classification over the other.

Thermal Insulation

FIREGUARD® tanks include lightweight thermal insulation material between the inner and outer steel tanks. This insulation is intended to limit heat transfer to the primary tank and the tank’s contents during fire exposure.

FLAMESHIELD® tanks are non-insulated. Their fire-tested performance is based on a tight-wrap double-wall design that has been tested to withstand the required fire exposure.

Fire Test Context

Both tank technologies are related to fire performance, but they are evaluated in different specification contexts.

FIREGUARD® is tied to UL 2085 protected tank requirements. UL 2085 includes fire exposure performance and physical protection criteria. The tank is subjected to a 2-hour, 2,000°F heat exposure and the tank interior temperatures are monitored during the test to confirm that the test limits are not exceeded.

FLAMESHIELD® is tied to SwRI 97-04 fire-tested performance. A 2-hour, 2,000°F fire test validates the performance of properly designed non-insulated double-wall tanks.

Impact and Ballistics Protection

FIREGUARD® includes ballistics and impact protection per UL 2085. This is an important reason FIREGUARD® may be selected for sites where physical damage, vehicle traffic, public exposure, or AHJ requirements are a concern.

FLAMESHIELD® is not positioned as a UL 2085 impact- and ballistics-protected tank. Site-specific physical protection, such as barriers or bollards, may still be required depending on the installation and local code requirements.

Secondary Containment and Leak Detection

Both FIREGUARD® and FLAMESHIELD® are double-wall tank systems that can provide secondary containment and interstitial monitoring capability.

For both technologies, the interstitial space can be monitored for leak detection. This helps owners and operators detect a release from the primary tank before product reaches the environment.

Emergency Venting

Emergency venting is an important specification and inspection issue for aboveground storage tanks.

UL 2085 tanks, including FIREGUARD® tanks, are required to be shipped from the fabricator with UL listed emergency vents on the primary and interstitial vent openings. FLAMESHIELD® tanks should also be evaluated for proper normal and emergency venting based on the tank design, stored product, applicable codes, and AHJ requirements.

Because venting requirements are technical and code-sensitive, they should be reviewed early with the tank manufacturer, project engineer, vent manufacturer, and authority having jurisdiction.

Siting and Code Review

FIREGUARD® may be preferred where a protected tank classification helps address fire exposure, physical damage protection, site constraints, separation distances, or AHJ expectations.

FLAMESHIELD® may be appropriate where a fire-tested double-wall tank satisfies the project requirements and the installation does not require a UL 2085 protected tank.

The authority having jurisdiction should be involved early because code interpretation, required protection, setbacks, capacity limits, and installation conditions can vary by location.

When FIREGUARD® Tanks Are Typically Used

FIREGUARD® tanks are typically used when the project requires or benefits from a UL 2085 listed protected tank.

Application NeedWhy FIREGUARD® May Fit
UL 2085 protected tank requirementFIREGUARD® is a UL 2085 listed protected tank
Enhanced fire resistanceThe tank includes thermal insulation intended to limit heat transfer during fire exposure
Impact and ballistics protectionFIREGUARD® includes ballistics and impact protection per UL 2085
Integrated secondary containmentThe double-wall protected tank system includes secondary containment
Interstitial monitoringThe interstitial space can be monitored for leak detection
Constrained sitesA protected tank may help address code, AHJ, setback, or exposure concerns
Fuel storage applicationsFIREGUARD® is commonly used for aboveground storage of compatible fuels and combustible liquids
Long-term flexibilitySteel construction supports compartments, customization, relocation, repair, and recycling

When FLAMESHIELD® Tanks Are Typically Used

FLAMESHIELD® tanks are typically used when a fire-tested, double-wall aboveground storage tank is appropriate, and UL 2085 protected tank status is not required.

Application NeedWhy FLAMESHIELD® May Fit
Fire-tested double-wall tankFLAMESHIELD® has 2-hour, 2,000°F fire-tested performance under SwRI 97-04
Built-in secondary containmentThe tight-wrap double-wall design provides secondary containment
Interstitial monitoringThe interstitial space can be monitored for leak detection
UL 142 double-wall tank contextThe primary and secondary containment are manufactured and listed under UL 142
Non-insulated designThe SwRI 97-04 fire test validates performance of non-insulated tanks
Fuel and chemical compatibilityThe primary storage tank and secondary containment are compatible with a wide range of fuels and chemicals
Project cost and customizationSteel construction supports compartments, customization, relocation, and fabrication flexibility

Why FIREGUARD® May Be Required or Preferred

FIREGUARD® may be required or preferred when the project calls for a UL 2085 listed protected aboveground tank. This can be driven by fire code requirements, AHJ interpretation, insurance requirements, owner standards, site constraints, proximity to property lines or buildings, vehicle traffic, or critical fuel storage needs.

FIREGUARD® may be a strong choice when the project requires:

Decision FactorFIREGUARD® Advantage
Protected tank listingFIREGUARD® is UL 2085 listed as a protected aboveground storage tank
Fire exposure performanceThe insulated design is intended to limit heat transfer to the primary tank during fire exposure
Physical damage protectionFIREGUARD® includes impact and ballistics protection per UL 2085
Secondary containmentThe double-wall protected tank system includes secondary containment
Leak detectionThe interstitial space can be monitored
Code and AHJ acceptanceFIREGUARD® may help address protected tank requirements in certain installations
Fuel compatibilityFIREGUARD® can be used with a wide range of compatible fuels and chemicals
Steel constructionSteel allows for sustainability, compartments, customization, repair, and relocation

Why FLAMESHIELD® May Be Preferred

FLAMESHIELD® may be preferred when a project needs a fire-tested, double-wall aboveground tank but does not require a UL 2085 protected tank.

FLAMESHIELD® may be a strong choice when the project requires:

Decision FactorFLAMESHIELD® Advantage
Fire-tested performanceFLAMESHIELD® has 2-hour, 2,000°F fire-tested performance under SwRI 97-04
Double-wall containmentThe tight-wrap design provides built-in secondary containment
Leak detectionThe interstitial space can be monitored
UL 142 tank contextThe primary and secondary containment are manufactured and listed under UL 142
Non-insulated configurationFire-tested performance is validated for a non-insulated tank design
Design flexibilityAvailable in horizontal, vertical, rectangular, and diked designs
Lower-weight fire-tested designBecause FLAMESHIELD® tanks weigh less than comparable UL 2085 listed protected tanks, they may be easier to ship, handle, and place while still providing fire-tested double-wall performance.
Steel constructionSteel supports sustainability, compartments, customization, repair, and relocation

Common Confusion Points

Are FIREGUARD® and FLAMESHIELD® the same thing?

No. Both are STI/SPFA aboveground steel tank technologies, and both are related to fire performance, but they are not the same. FIREGUARD® is a UL 2085 listed protected tank. FLAMESHIELD® is a fire-tested, double-wall aboveground tank tested under SwRI 97-04.

Is FLAMESHIELD® a UL 2085 tank?

No. FLAMESHIELD® should not be described as a UL 2085 protected tank. It is a fire-tested, double-wall UL 142 aboveground tank with SwRI 97-04 fire-tested performance.

Is FIREGUARD® just a fire-tested tank?

No. FIREGUARD® is more specifically a UL 2085 listed protected tank. It includes thermal insulation and impact and ballistics protection per UL 2085.

Do both tanks provide secondary containment?

Yes. Both FIREGUARD® and FLAMESHIELD® are double-wall tank systems with secondary containment and interstitial monitoring capability.

Do both tanks have insulation?

No. FIREGUARD® includes lightweight thermal insulation between the inner and outer steel tanks. FLAMESHIELD® is a non-insulated tight-wrap double-wall tank.

Which tank should be specified?

The right tank depends on the stored liquid, capacity, site layout, fire exposure, impact exposure, separation distances, applicable codes, owner requirements, and AHJ interpretation. If the project requires a UL 2085 protected tank, FIREGUARD® is the appropriate STI/SPFA technology. If the project requires a fire-tested double-wall tank and UL 2085 protected tank status is not required, FLAMESHIELD® may be appropriate.

FAQs

Related Resources

FIREGUARD®

FLAMESHIELD®

UL 142 vs. UL 2085 Aboveground Storage Tanks

What Is UL 2085?

When Is UL 2085 Required for Aboveground Storage Tanks?

STI Technologies

STI Standards

Shop-Fabricated Tank Manufacturers

Determine the Right Tank for Your Project

STI/SPFA members fabricate aboveground steel storage tanks for fuel, petroleum, commercial, industrial, and regulated storage applications. Learn more about STI/SPFA tank technologies for your next project.