This project is a new pipeline that attaches two existing clearwells to an additional new clearwell. It consists of approximately 1800 lineal feet of 86 3/4″ O.D. spiral welded steel pipe at 1/2″ thickness except at valves where pipe wall thickness was required to be at 1″ thick for a minimum distance of 7′-2″ on either side of the valves.
Pipe was coated with AWWA C222 polyurethane at a minimum thickness of 25 mils and lined with AWWA C205 Cement Mortar at a thickness of 1/2″. Both the polyurethane and cement mortar was applied in house.
All materials in contact with water are certified to NSF-61 standards for potable drinking water.
The project contained the following:
(14) Flexible couplings with AWWA M11 Harness Restraints
(19) AWWA C207 Class ‘E’ Flange connections
(65) Bell and Spigot Lap Welds
(1) 86 3/4″ O.D. x 57 1/8″ O.D. Eccentric Reducer 10′-0″ long
(1) 86 3/4″ O.D. x 62 3/4″ O.D. Eccentric Reducer 4′-0″ long
(5) 86 3/4″ O.D. size on size tees
(4) 86 3/4″ O.D. Dished Heads
(17) 86 3/4″ O.D. Multi section mitered elbows
Standards followed:
AWWA C200
AWWA C205
AWWA C207
AWWA C208
AWWA C210
AWWA C219
AWWA C220
M11 (Latest Edition)
Award Name
Pipeline Project
Company Name
Mid America Pipe Fabricating & Supply, LLC
Award Year
2022
Product Details
- Wyckoff WTP Clearwell #3
- Cobb County - Marietta Water Authority
- Acworth, GA
Date Completed
December 1, 2022
Construction Standard
AWWA C200
Diameter
86 3/4"
Steel Tonnage Used
420
Steel Thickness
1/2" & 1"
Steel Fitting Type
AWWA C208 / M11